Repository logo
 

Wind-tunnel study of exhaust-intake cross contamination and dispersion of rooftop emissions, Hospital of the University of Pennsylvania: HUP phase IV

dc.contributor.authorPeterka, J. A. (Jon A.), author
dc.contributor.authorCermak, Jack E., author
dc.contributor.authorFluid Mechanics and Wind Engineering Program, Fluid Dynamics and Diffusion Laboratory, Department of Civil Engineering, Colorado State University, publisher
dc.coverage.spatialPhiladelphia (Pa.)
dc.date.accessioned2007-01-03T07:15:35Z
dc.date.available2007-01-03T07:15:35Z
dc.date.issued1984-07
dc.descriptionIncludes bibliographical references.
dc.descriptionCSU Project 2-95750.
dc.descriptionFor Hospital of the University of Pennsylvania, Philadelphia, Pennsylvania.
dc.descriptionCER84-85JEC-JAP1.
dc.descriptionCER84-85JEC-JAP1a (Appendices).
dc.descriptionJuly 1984, Modified March 1985.
dc.description.abstractA wind-tunnel study on a 1:250 scale model of a planned Phase IV addition to the Hospital of the University of Pennsylvania complex and the nearby structures was completed in the Fluid Dynamics and Diffusion Laboratory at Colorado State University. The study was accomplished to determine the concentration of effluents, emitted from various exhausts near and on the proposed addition, at various air intakes and other critical locations. Tracers emitted from individually modelled sources were sampled at 47 receptors for each of eight wind directions to measure the extent of exhaust-intake cross-contamination and dispersion of roof-top emissions. Some "follow-on" tests were also performed with a modified model to determine effluent concentrations at the HUP IV penthouse from selected nearby sources. Additional wind-tunnel testing included velocity measurements to determine mean and gust winds at selected locations in the vicinity of the Hospital. The pedestrian-level wind data were recorded at 18 different locations for each of 16 wind directions. Selected test conditions were identified for inclusion in a visualization study. Visible smoke plumes, generated at locales of special interest, were recorded on VHS format video cassettes. The concentration data revealed that the complex contains regions where the air is relatively stagnant. Exhaust gases in these regions experience little, if any, sweeping action from the wind, from any direction, to enhance dispersion. Some interaction between area exhausts and intakes situated on the Phase IV addition, was measured. Any adverse contamination of intake air is dependent upon composition of the exhaust effluents. The velocity measurements indicated that the new structure should not induce any significant wind related problems for pedestrian traffic in the surrounding area.
dc.format.mediumreports
dc.identifier.urihttp://hdl.handle.net/10217/90279
dc.languageEnglish
dc.language.isoeng
dc.publisherColorado State University. Libraries
dc.relationCatalog record number (MMS ID): 991012061989703361
dc.relationTA7.C6 CER 84/85-1
dc.relation.ispartofCivil Engineering Reports
dc.relation.ispartofCER, 84/85-1, 1a
dc.rightsCopyright and other restrictions may apply. User is responsible for compliance with all applicable laws. For information about copyright law, please see https://libguides.colostate.edu/copyright.
dc.subjectPhiladelphia (Pa.) -- Buildings, structures, etc.
dc.subjectWind tunnel models
dc.subjectBuildings -- Pennsylvania -- Philadelphia -- Aerodynamics
dc.titleWind-tunnel study of exhaust-intake cross contamination and dispersion of rooftop emissions, Hospital of the University of Pennsylvania: HUP phase IV
dc.typeText
dcterms.rights.dplaThis Item is protected by copyright and/or related rights (https://rightsstatements.org/vocab/InC/1.0/). You are free to use this Item in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s).

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
CER_Cermak_Peterka_2-3.pdf
Size:
19.07 MB
Format:
Adobe Portable Document Format
Description: