Repository logo
 

Generalized pressure drop and heat transfer correlations for jet impingement cooling with jet adjacent fluid extraction

dc.contributor.authorHobby, David Ryan, author
dc.contributor.authorBandhauer, Todd M., advisor
dc.contributor.authorOlsen, Daniel B., committee member
dc.contributor.authorPrawel, David, committee member
dc.contributor.authorVenayagamoorthy, Karan, committee member
dc.date.accessioned2022-05-30T10:22:35Z
dc.date.available2022-05-30T10:22:35Z
dc.date.issued2022
dc.description.abstractJet impingement technologies offer a promising solution to thermal management challenges across multiple fields and applications. Single jets and conventional impinging arrays have been studied extensively and are broadly recognized for achieving extraordinary local heat transfer coefficients. This, in combination with the versatility of impinging arrays, has facilitated a steady incline in the popularity of jet impingement investigations. However, it is well documented that interactions between adjacent jets in an impinging array have a debilitating effect on thermal performance. Recently, in an attempt to mitigate the jet interference problem, a number of researchers have created innovative jet impingement solutions which eliminate crossflow effects by introducing fluid extraction ports interspersed throughout the impinging array. This novel adaptation on classical impinging arrays has been shown to produce dramatically improved thermal performance and offers an excellent opportunity for future high-performing thermal management devices. The advent of jet-adjacent fluid extraction in impinging arrays presents a promising improvement to impingement cooling technologies. However, there have been very few investigations to quantify these effects. Notably, the current archive of literature is severely lacking in useful, predictive correlations for heat transfer and pressure drop which can reliably describe the performance of such impinging arrays. Steady-state heat transfer and adiabatic pressure drop experiments were conducted using nine unique geometric configurations of a novel jet impingement device developed in this work. This investigation proposes novel empirical correlations for Darcy friction factor and Nusselt number in an impingement array with interspersed fluid extraction ports. The correlations cover a broad range of geometric parameters, including non-dimensional jet array spacing (S/Dj) ranging from 2.7 to 9.1, and non-dimensional jet heights (H/Dj) ranging from 0.31 to 4.4. Experiments included jet Reynolds numbers ranging from 70 to 24,000, incorporating laminar and turbulent flow regimes. Multiple fluids were tested with Prandtl numbers ranging from 0.7 to 21. The correlations presented in this work are the most comprehensive to date for impinging jet arrays with interspersed fluid extraction. Nusselt number was found to be correlated to impinging jet Reynolds number to the power of 0.57. The resulting correlation was able to predict 93% of experimental data within ±25%. During adiabatic pressure drop experiments, multiple laminar-turbulent flow transition regions were identified at various stages in the complex jet impingement flow path. The proposed Darcy friction factor correlation was separated into laminar, turbulent, and transition regions and predicted experimental data with a mean absolute deviation of 20%. The heat transfer and pressure drop correlations proposed in this investigation were used in a follow-on optimization study which targeted an exemplary impingement cooling application. The optimization study applied core experimental findings to a microchip cooling case study and evaluated the effects of geometry, flow, and heat load parameters on cooling efficiency and effectiveness. It was discovered that reducing non-dimensional jet height results in all-around improved cooling performance. Conversely, low non-dimensional jet spacing results in highly efficient but less effective solutions while high non-dimensional jet spacing results in effective but less efficient cooling.
dc.format.mediumborn digital
dc.format.mediumdoctoral dissertations
dc.identifierHobby_colostate_0053A_17073.pdf
dc.identifier.urihttps://hdl.handle.net/10217/235294
dc.languageEnglish
dc.language.isoeng
dc.publisherColorado State University. Libraries
dc.relation.ispartof2020-
dc.rightsCopyright and other restrictions may apply. User is responsible for compliance with all applicable laws. For information about copyright law, please see https://libguides.colostate.edu/copyright.
dc.subjectheat transfer
dc.subjectjet impingement
dc.subjectcorrelation
dc.subjectpressure drop
dc.subjectimpinging
dc.titleGeneralized pressure drop and heat transfer correlations for jet impingement cooling with jet adjacent fluid extraction
dc.typeText
dcterms.rights.dplaThis Item is protected by copyright and/or related rights (https://rightsstatements.org/vocab/InC/1.0/). You are free to use this Item in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s).
thesis.degree.disciplineMechanical Engineering
thesis.degree.grantorColorado State University
thesis.degree.levelDoctoral
thesis.degree.nameDoctor of Philosophy (Ph.D.)

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Hobby_colostate_0053A_17073.pdf
Size:
11.86 MB
Format:
Adobe Portable Document Format